Page 40 of 51 Parameter change in the web edge sensor bks+
TEACH-IN-METHODEN
To adjust the zero position of the edge to be controlled, the sensor can be calibrated with two options.
Completely freeing the fork from the web material
push , then completely fill sensor fork and
push .
Or align the web edge inside the fork with the two marks to ensure a 50 % coverage of the sound path,
then push .
Ready.
ANALOG OUTPUT SETTING
The analog output can be adjusted so that it supplies current or voltage. The characteristic can be
selected as rising or falling.
Voltage / Current Increasing: voltage / current increases with higher coverage
Voltage / Current falling: voltage / current drops with higher coverage
SWITCH OUTPUT SETTING
The switched output of the bks+../FIU or bks+../F can be used e.g. for monitoring purposes. He switches
around the (adjustable) center in a (adjustable) window.